Single-phase Hybrid Solar Inverter
| BD6KTL-RH1N | BD8KTL-RH1N | BD10KTL-RH1N | BD12KTL-RH1N | |
| Input (PV) | ||||
| Max. Input Power | 7.8kW | 10.4kW | 13kW | 15.6kW |
| Max. DC Voltage | 500V | |||
| MPP Voltage Range | 125V~500V | |||
| Max. PV Input Current | 12A | |||
| Number of MPP Trackers / String per MPPT | 4 /1 | |||
| Output (AC) | ||||
| Max. Output Current | 27.3A | 36.4A | 45.4A | 50A |
| Rated AC Output Power | 6kVA | 8kVA | 10kVA | 11.4kVA |
| AC Output Voltage | 240V | |||
| Grid Voltage Range | 211V~264V | |||
| Frequency | 50Hz / 60Hz | |||
| Power Factor | 0.8 lagging~0.8 leading | |||
| THDi | <3% | |||
| Topology | L+N+PE | |||
| Output (EPS) | ||||
| Rated Output Power | 6kVA | 8kVA | 10kVA | 12kVA |
| Rated Output Voltage | 220V~240V / 110V~120V | |||
| Overload Capacity | 110%, 30S / 120%, 10S / 150%, 0.02S | |||
| Automatic Switching Time | <20ms | |||
| Frenquency | 50Hz / 60Hz | |||
| THDu | <2% | |||
| Battery | ||||
| Battery Voltage Range | 85V~400V | |||
| Max. Charging Voltage | 400V | |||
| Max. Charge / Discharge Current | 80A / 80A | |||
| Battery Type | Lithium / Lead-acid | |||
| Communication | CAN / RS485 | |||
| Efficiency | ||||
| Max. Efficiency | ≥98.2% | |||
| CEC Efficiency | ≥97.2% | |||
| Communication | ||||
| Display | LCD | |||
| Communication | Standard: RS485 / CAN / DRM Optional: Wifi / 4G |
|||
| Standard Compliance | ||||
| Safty | UL1741SA all options, UL1699B, CSA 22.2 | |||
| EMC | FCC Part 15, Class B | |||
| On Grid | IEEE 1547, IEEE 2030.5, Hawaii Rule 14H, Rule 21 Phase I,II,III | |||
| General Data | ||||
| Dimensions (W x H x D) | 530 x 660 x 200 mm | |||
| Weight | 32kg | |||
| Operation Temperature | -25℃~60℃ | |||
| Cooling Method | Natural Cooling | |||
| Protection Degree | IP65 / NEMA 3R | |||
| Noise Emission | <25dB | <29dB | ||
| Max. Operating Altitude | 2000m | |||
| Relative Humidity | 0 ~95% (non-condensing) | |||
| Topology | Transformerless | |||
| Standby Power Consumption | <2.5W (With the battery <5W ) | |||